How much steam can a Storage Boiler deliver?

Each Heat Cell delivers 2 t/h of steam continuously (about 1.3 MWth) across its full state of charge. When the store is more than 75% charged it can deliver up to 6 t/h (about 3.9 MWth) for shorter periods. The minimum output is 0.2 t/h, giving a turndown ratio of 10:1.

Output scales with the number of cells. A two-cell system delivers 4 t/h continuously and 12 t/h at peak; an eight-cell system, 16 t/h continuously and up to 48 t/h at peak. The conversion is about 0.65 MW per t/h at 6 bar with 80°C feedwater.

The peaking capability matters because many sites have short periods of very high steam draw, such as a brew or a sterilisation cycle starting. Sizing a plant for those peaks is where much of the capital goes; typically 60% of the capital cost of a steam system delivers only 20% of the energy. With a Caldera Storage Boiler the store covers the peak, so the rest of the plant and the grid connection do not have to be sized for it. The control system keeps the store at a high state of charge ahead of a known peak. How long a peak can be sustained depends on the starting state of charge, and this is part of Caldera's site modelling.