What electrical connection does a Storage Boiler need?
The Storage Boiler needs a medium-voltage supply at 11, 20 or 33 kV, stepped down to 690 V or 400 V. If your site does not have a suitable transformer, Caldera can supply one as part of the system.
Each Heat Cell has its own power and control module and its own electrical feed: up to 2 MWe at 690 V, or 1.3 MWe at 400 V. This allows the Heat Cells to be operated independently, and allows maintenance on one cell without interrupting the operation of the rest. The balance of plant takes a small 400 V supply.
A key difference between a direct electric boiler and the Caldera Storage Boiler is the size of the grid connection, transformers and capacity charges. With an electric boiler the energy draw follows the steam demand, so the import capacity, transformers and capacity charges are all sized to supply the peaks. With a Caldera Storage Boiler the store charges steadily over several hours and covers the peaks from stored heat, so the import capacity is sized to your average steam load rather than the peak. Many sites can therefore connect a Caldera Storage Boiler within the supply headroom they already have.