What is the turndown ratio, and how does the system follow demand?

The turndown ratio is 10:1. A single Heat Cell can modulate from 2 t/h down to 0.2 t/h, and a system with several cells can turn down further by taking cells out of service.

The system follows your steam header pressure, in the same way your existing boilers do. When demand rises, header pressure falls and the feedwater control valve opens to raise more steam; when demand falls, the valve closes. At very low demand the controls drop individual heating columns out of service and rotate them, and below the minimum output the cell cycles on and off against header pressure. No operator intervention is needed, as the whole process is automated in the intelligent controls, and none of it interrupts the supply to your steam header.